Making A Case For VFD

By Brian James and Roger Weldon   

HVAC Systems Plumbing

The benefits of packaged pump systems and variable flow pressure boosting.

Packaged pump systems can be defined as a complete assembly of pumping components needed for a system that is wired, piped, and mounted on a base. This compact, space-saving configuration offers easy installation, single source responsibility, and advanced control options with communication ability.

VARIABLE FLOW REQUIREMENTS

Domestic water supply systems have variable flow demands and can save energy with variable frequency drive (VFD) controlled pumps. There is an opportunity with existing pump installations to discover the true state of the system by performing a pump audit. A pump audit determines the consumption flow profile and energy usage that the installation experiences during normal operation. Acquiring a flow profile for an existing system provides the precise data required to design the optimum system for the application. A system designed with pump audit data will lead to a highly efficient design; hence lower, cost of ownership. New installations typically use plumbing fixture counts and the Hunter’s Curve for sizing the pump system, as recommended or required by inspectors or local codes. This method can lead to oversized pumps or pump systems, and does not address the variable flow requirement for the domestic water supply. The flow profile in Figure 1 indicates that the demand increases in the morning and in the afternoon to the maximum flow, and gradually drops off and stops in the night hours. Peak flow is required for three hours of the day. Most of the time the flow is less than 50 per cent of peak flow. In this example, a pump system with two 50 per cent pumps would match the flow profile compared to a single 100 per cent pump, and would ensure that the system operates near peak efficiency. One 100% pump would run near peak efficiency for less than half of the time. This example shows relatively small flow requirements, but the same holds true for larger flows where even more energy can be saved.

VFD-CONTROLLED PUMPS

The Affinity Laws state how a pump’s performance changes with changing pump speed (RPM).

Small reductions in pump speed can create large reductions in brake horsepower (BHP). The BHP changes by factor of the cube of the speed change ratio. Figures 2-4 show an example of a constant pressure application with two different flow rates, comparing a VFD-controlled pump to a fixed speed pump with a pressure regulating valve. In this application, 116 ft. constant pressure is required at 180 GPM and 90 GPM.

Figure 3 demonstrates that the pump requires 3.77 HP at 85 per cent speed using VFD control to achieve 90 GPM. Figure 4 illustrates a curve for a constant speed pump and a pressure regulating valve (PRV) to maintain the required pressure (116 ft.). This system builds 167 ft. of pressure at 90 GPM and uses 5.7 BHP. The extra pressure is reduced by the PRV. However, the PRV wastes energy and requires periodic maintenance. This can be eliminated with VFD-controlled pumps.

Based on the flow profile in Figure 1, a VFD system saves $750 in energy cost compared to a PRV system. The calculation is based on 24/7 operation with a $0.10 KWh energy cost and 85 per cent VFD and motor efficiency. A system with relatively low speed reduction (15 per cent) saves significant energy.

VFD-controlled systems allow precise control of the discharge pressure. Other advantages include:

• Flexibility to electronically “trim” (no oversize/undersize concerns)

• Soft starting of motors (no motor cycling issues)

• Smooth, controlled performance ramp up/down (less
mechanical problems/maintenance)

• System turns itself off at low or no flow (additional energy savings)

CHOOSING THE RIGHT PUMP(S)

Pump selection for variable flow versus single duty point has different requirements. A single duty point requires the selection of a pump at the best efficiency point (BEP), where pumps have the highest life expectancy. Variable flow applications require multiple duty points. For variable flow service, consider the following:

• NPSH available

• Possibility of over or undersized system

• Pump type – single or multiple impeller

The rule of thumb for selecting pumps for variable flow service is to select a pump at the right of BEP. Selecting a pump to the right of BEP will allow the pump(s) to stay in the best efficiency range at lower flow demands. The down side for selecting a pump to the right of BEP is increased NPSH requirement. In some cases, due to NPSH available, a pump selection at the right of BEP may not be suitable. Pump type is another consideration. Single impeller pumps typically have a flatter curve compared to multiple impeller pumps, and are less forgiving in situations where conditions change and the pumps are undersized. An oversized pump with VFD control can be electronically “trimmed” by speed reduction. The steeper curve of a multiple impeller pump allows for more speed reduction ratio at lower flows, increases the pump’s flexibility to meet a changing design pressure requirement, and allows higher energy savings. Multistage pumps, by design, are more service-friendly than single impeller end suction pumps. The multistage pump, together with VFD control, is an ideal choice for variable flow pressure boosting.

PROPORTIONAL PRESSURE CONTROL

Municipal domestic water pump systems have a high head requirement dedicated to pipe friction loss. Pipe friction loss compensation via proportional pressure control provides significant savings and reduces problems associated with high pressure, which can occur when flow rates are low compared to the design conditions. Pump systems typically are oversized due to a conservative head loss calculation and additional safety margins. Municipal pump systems with large pipe networks are often oversized intentionally to prepare for future growth. The head required for the pump system includes the pipe friction head based on future high flow design conditions. This can result in a large pump system that has the possibility of using more energy than it should. Figure 5 shows a four-pump system with a maximum design condition of 2200 gpm at 266 ft. If the design pipe friction loss of the system is 20 per cent of the total required boost pressure (266 ft.), the actual pressure boost requirement at 400 GPM is 212 ft. Proportional pressure control decreases pressure at lower flows and increases it at higher flows to compensate for pipe friction loss. If the pump system operates 24/7 at 400 GPM for 50 per cent of the time, at $0.10 KWh, an annual savings of $2592 results, based on an overall motor/VFD efficiency of 88 per cent. In addition to energy savings, proportional pressure control reduces leaks and saves water at low flow periods by reducing the system pressure.

CONCLUSION

VFD-controlled pump systems offer pressure control with energy savings and the ability to match the flow consumption profile without waste. Systems with multiple pumps deliver variable flow requirements at BEP range. It is important to identify the flow consumption profile of the installation. If the flow rate is constant, a single service duty pump might be the solution. Even for these applications, VFD-controlled pump systems may be justified with reduced maintenance costs.  <>

Brian James P.E., is a product specialist and Roger Weldon is a service engineer with Grundfos.